This product is suitable for use in power systems, control and monitoring circuits with low-smoke halogen-free requirements, at rated voltages of 600/1000V and below.Second file:Rated voltage U0/U: 600/1000V.Long-term allowable operating temperature of the cable: 90°C.The cable installation tempera
This product is suitable for use in power systems, control and monitoring circuits with low-smoke halogen-free requirements, at rated voltages of 600/1000V and below.
Second file:
Rated voltage U0/U: 600/1000V.
Long-term allowable operating temperature of the cable: 90°C.
The cable installation temperature shall not be lower than 0°C. Recommended bending radius:
Halogen-Free Flame-Retardant Control Cable:
① Cables with armor and steel tape shielding structure: bending radius shall not be less than 12 times the cable outer diameter;
② Cables with other structures: bending radius shall not be less than 6 times the cable outer diameter.
Halogen-Free Flame-Retardant Power Cable:
① Single-core cable: bending radius shall not be less than 20 times the cable outer diameter;
② Multi-core cable: bending radius shall not be less than 15 times the cable outer diameter.