One-stop comprehensive solution provider
This product is suitable for use as a power transmission line for electrical equipment in high-temperature environments and harsh conditions, at rated voltages of 0.6/1kV and below.Rated voltage U0/U: 0.6/1kV.Maximum allowable operating temperature of the cable: 200°C for fluoroplastic insulation a
This product is suitable for use as a power transmission line for electrical equipment in high-temperature environments and harsh conditions, at rated voltages of 0.6/1kV and below.
Rated voltage U0/U: 0.6/1kV.
Maximum allowable operating temperature of the cable: 200°C for fluoroplastic insulation and sheath; 105°C for fluoroplastic insulation with heat-resistant 105°C PVC sheath; 180°C for fluoroplastic insulation with silicone rubber sheath.
During a short circuit (maximum duration not exceeding 5 seconds), the maximum temperature of the cable conductor shall not exceed 250°C.
The cable installation temperature shall not be lower than -15°C.
The bending radius of the cable is as follows: Single-core cable: its bending radius shall not be less than 20D of the cable outer diameter. Three-core cable: its bending radius shall not be less than 15D of the cable outer diameter.
Fluoroplastic insulated and sheathed power cables offer excellent chemical corrosion resistance, high-temperature resistance, and flame retardancy.